Dealerships

Rogowski Coil MFC140
Rogowski Coil MFC140

The Rogowski Coil MFC140 (7 mm cross-section) is a flexible current transducer based on the Rogowski principle. MFC140 coils are available in different sizes and can be supplied according to the customer's design, therefore they can be used in all applications where traditional transducers do not fit due to their size and/or weight.
The MFC140 coil is equipped with a shield against the influence of external magnetic fields, therefore it ensures stable measurement from low currents up to hundreds of kA.
The MFC140 is also available with a built-in integrator, without the need for external devices for 90° phase shift compensation and frequency equalization. This is an advantage because there are no external boxes, providing ease of use.

TECHNICAL SPECIFICATIONS

Transducer

Coil length: 15 ... 50 cm
Cord diameter: 7.2 ±0.2 mm
Fastening: bayonet holder
Weight: 150 – 500 g
Material: Polyphenylene and thermoplastic elastomer

Electrical characteristics for model without integrator

Rated output level: 100 mV / kA @ 50 Hz (RMS values)
Max measurable current:
600 A for coil length 15 ... 28 cm
2500 A for coil length 29 ... 41 cm
5000 A for coil length 42 ... 50 cm
Coil resistance: 170 ... 690 Ω
Accuracy: Class 1-A1 according to IEC 61869-10
Frequency: 50/60 Hz
Overvoltage category: 1000 V CAT III, 600 V CAT IV
Pollution degree: 3
Insulation test voltage: 7400 VRMS / 5 s

Electrical characteristics for model with integrator

Power supply: 4 ... 26 VDC
Max consumption: 5 mADC
Rated output level: 333 mV / FS (RMS values)
FS depends on model: 200, 250, 600, 1000 A
Positioning error: Better than ±1% of reading
Frequency: 50/60 Hz
Overvoltage category: 1000 V CAT III, 600 V CAT IV
Pollution degree: 3
Insulation test voltage: 7400 VRMS / 5 s

Connection cable for model with integrator

Type: 5 x 22 AWG shielded
Length: 3 m. Others on request: 5, 7, 10, 15 m

Connection cable for model without integrator

Type: 3 x 22 AWG shielded
Length: 3 m. Others on request: 5, 7, 10, 15 m

Environmental conditions

Protection degree: IP68
Operating temperature: -40 ... +75°C
-40 ... +60°C up to 2500 A for coil length 15 ... 41 cm
up to 5000 A for coil length 42 ... 50 cm

Standards compliance

IEC standards: IEC 61010-1, IEC 61010-2-032, IEC 60529